Összesen 1 találat.
#/oldal:
Részletezés:
Rendezés:

1.

001-es BibID:BIBFORM031083
Első szerző:Váradiné Szarka Angéla (fizikus)
Cím:Measuring harmonic distortion in electrical power networks : New approach / Angela Varadine Szarka
Dátum:2010
ISSN:0263-2241
Megjegyzések:Standard specification for power network quality diagnostic systems requires synchronisation of sampling rate to the network frequency in every 10 second in order to ensure high accuracy of harmonic analysis. The total harmonic distortion (THD) cumulates measurement errors, therefore, it is the most sensitive parameter to the frequency synchronisation. This paper investigates two main effects putting impact on the THD computation accuracy. The first is the effect of the base clock rate of sampling hardware and the second is the practical deviation of network frequency during the 10 second synchronisation period. The relative accuracy of THD calculation is examined in different real practical solutions and different synchronisation methods are discussed and assessed. Theoretical proof and practical demonstration are given to show the needs of special synchronisation methods in certain measuring circumstances.
Tárgyszavak:Műszaki tudományok Villamosmérnöki tudományok idegen nyelvű folyóiratközlemény külföldi lapban
Technológia Transzfer és Infrastruktúra Hasznosítás
power network diagnostics
quality assessment
frequency analysis
total harmonic distortion
Megjelenés:Measurement. - 43 : 10 (2010), p. 1628-1635. -
Pályázati támogatás:TÁMOP-4.2.1/B-09/1/KONV-2010-0007
TÁMOP
Internet cím:Szerző által megadott URL
DOI
Intézményi repozitóriumban (DEA) tárolt változat
Borító: